How to plan the electrics of an apartment

From the hallway light to the induction hob. Split the flat into sensible circuits, choose 30 mA protection and get a clear draft to discuss with your electrician.

7 min readUpdated October 2026
APARTMENT / 01single-phase · 50 A
Panel generated by PlanMyPanel for the example: Apartment, single-phase 50 A
Generated by the planner9 outgoing circuits
One plan. Wiring, shopping list and assembly steps.
01

Before you start

Four facts decide most of the plan. You can read them off the existing panel, the meter cabinet or your supply contract.

02

Typical apartment circuits

One circuit per job: lighting, sockets by room, and a line of its own for every large appliance. This is how the example below is split.

EXAMPLE CIRCUIT SCHEDULECopper conductors · 230 V circuits
Example circuits. Copper cable sections in square millimetres; verify sizing and protection for each installation.
CircuitBreakerCable mm²ProtectionNote
Lighting · living room, bedroom, hallB103 × 1.5RCBO 30 mADry rooms share one lighting circuit.
Lighting · kitchen and bathroomB103 × 1.5RCBO 30 mAWet rooms get their own lighting zone.
Living room socketsB163 × 2.5RCBO 30 mATV, computer and chargers; about 5–6 points per circuit.
Bedroom socketsB163 × 2.5RCBO 30 mARooms with more than two points get their own line.
Kitchen worktop socketsB163 × 2.5RCBO 30 mAKettle, microwave and coffee machine run together.
Bathroom socketB163 × 2.5RCBO 30 mAOutside zones 0–2, with a splash-proof cover.
Induction hob 7 kWB323 × 6Own RCBO 30 mASingle phase: 32 A and 6 mm²; never on a socket circuit.
Washing machineB163 × 2.5Own RCBO 30 mALong cycles near water; type A at least.

Lighting · living room, bedroom, hall

Breaker
B10
Cable · mm²
3 × 1.5
Protection
RCBO 30 mA

Dry rooms share one lighting circuit.

Lighting · kitchen and bathroom

Breaker
B10
Cable · mm²
3 × 1.5
Protection
RCBO 30 mA

Wet rooms get their own lighting zone.

Living room sockets

Breaker
B16
Cable · mm²
3 × 2.5
Protection
RCBO 30 mA

TV, computer and chargers; about 5–6 points per circuit.

Bedroom sockets

Breaker
B16
Cable · mm²
3 × 2.5
Protection
RCBO 30 mA

Rooms with more than two points get their own line.

Kitchen worktop sockets

Breaker
B16
Cable · mm²
3 × 2.5
Protection
RCBO 30 mA

Kettle, microwave and coffee machine run together.

Bathroom socket

Breaker
B16
Cable · mm²
3 × 2.5
Protection
RCBO 30 mA

Outside zones 0–2, with a splash-proof cover.

Induction hob 7 kW

Breaker
B32
Cable · mm²
3 × 6
Protection
Own RCBO 30 mA

Single phase: 32 A and 6 mm²; never on a socket circuit.

Washing machine

Breaker
B16
Cable · mm²
3 × 2.5
Protection
Own RCBO 30 mA

Long cycles near water; type A at least.

Values from the worked example below, not a cable-sizing calculation. Check installation method, cable length, grouping and fault current on site. A hob connected across two or three phases needs a different breaker and cable. The table leaves out the example’s hallway socket circuit (B16).

03

A plan, made tangible

Here is a typical one-bedroom flat with an electric kitchen. Every circuit has its own RCBO, so one fault switches off one circuit only.

WORKED EXAMPLE

Apartment, single-phase 50 A

Living room, bedroom, kitchen with an induction hob, bathroom with a washing machine, hallway.

APARTMENT / 01single-phase · 50 A
Panel generated by PlanMyPanel for the example: Apartment, single-phase 50 A
Generated by the planner9 outgoing circuits
26/36modules used
9outgoing circuits
Estimated phase loadof 50 A
L1
46.6 A
THE SHORT SHOPPING LIST
  • 1×Enclosure 2×18 (36 modules), plastic, flush mounting, IP30
  • 1×Main breaker, C50, 2 mod.
  • 1×Surge protection device (SPD), type 2, 1+1 (CT2), 2 mod.
  • 1×Voltage relay, 2 mod.
  • 1×Distribution block 2P 125 A, 14 terminals per pole, 2 mod.
  • 2×RCBO, B10, 30 mA type A, 2 mod.

Generated by the planner from the answers above, with a 20% reserve target. Your apartment will differ: the final connection, measurements and sign-off belong to a licensed electrician.

04

Plan it, step by step

Six steps from a room list to a draft you can take to your electrician.

  1. 1

    Write down the supply

    Note the number of phases, the main breaker rating and whether a separate PE conductor comes into the panel. If a value is unknown, leave it open rather than guessing.

  2. 2

    List rooms and points

    Go room by room: light points, socket outlets and anything fixed to the wall. Add the sockets you wish you had today, not just the ones that exist.

  3. 3

    Give large appliances their own lines

    Hob, oven, water heater, washing machine and dishwasher each get a dedicated circuit with a breaker and cable sized to their rated power.

  4. 4

    Choose 30 mA protection

    Sockets, lighting and every bathroom circuit go behind 30 mA residual current protection. Individual RCBOs keep a fault on one circuit; shared RCDs cost less but switch off a whole group.

  5. 5

    Check the total against the main breaker

    Not everything runs at once, but the hob, oven and washing machine together can trip a 40 A supply. If the estimate is too high, ask the operator about more capacity.

  6. 6

    Export and hand over

    Export the wiring diagram, shopping list and assembly steps. A licensed electrician connects the panel to the supply, measures it and signs it off.

05

The details worth getting right

Requirements

HD 60364 / local rules

  • 30 mA RCD protection for socket outlets up to 32 A and for lighting in homes (HD 60364-4-41).
  • Every bathroom circuit behind a 30 mA RCD; no sockets in zones 0–2 (HD 60364-7-701).
  • Breaker matched to the cable, never the other way round.
  • In old TN-C buildings the PEN conductor is not split inside the apartment panel.
  • Connection to the supply, testing and sign-off by a licensed electrician.
Cable-sizing reference

Common mistakes

Small oversights, avoidable problems

  • −Lighting and sockets on one breaker.
  • −The hob plugged into the kitchen socket circuit.
  • −A bigger breaker to stop nuisance tripping instead of finding the fault.
  • −One RCD for the whole flat: a single leak switches off everything, including the fridge.
  • −A panel filled to the last module with no room for air conditioning later.
06

Common questions

How many circuits does an apartment need?

A one-bedroom flat typically ends up with 8 to 12 circuits. Count one or two lighting circuits, one socket circuit per room with more than two points, separate kitchen and bathroom socket circuits, plus one line for each large appliance. The example on this page has nine.

Which RCD should protect the bathroom?

A 30 mA RCD or RCBO, type A, on every circuit that serves the bathroom: lighting, sockets, water heater and washing machine. Type AC is no longer a good choice for modern appliances. Some washing machine makers recommend type F; follow the manual.

Does an induction hob need its own circuit?

Yes. A typical 7 kW hob on a single phase needs a dedicated 32 A breaker and 6 mm² copper cable. With a three-phase supply it is usually connected across two or three phases on a 5-core 2.5 mm² cable with a 16 A breaker. Check the connection options in the hob manual.

Is 40 A enough for an apartment with an electric kitchen?

Often not, once a hob, an oven and a washing machine are added. The example estimates about 47 A of demand, so it uses a 50 A main breaker. If your supply is smaller, plan fewer large loads at once or ask the network operator about more capacity.

RCDs or individual RCBOs in an apartment?

Both are correct when every circuit gets 30 mA protection. RCBOs cost more but a fault only switches off its own circuit. Shared RCDs are cheaper; split the circuits over at least two of them so lighting and the fridge do not go off together.

Can I build the apartment panel myself?

You can plan it, buy the parts and mount the devices on the rail. The connection to the supply, insulation and loop measurements and the sign-off belong to a licensed electrician; in many buildings the meter isolator is sealed by the network operator.