PlanMyPanel
All articles

Earthing systems: TN-S, TN-C-S, TT — and what if there is no PE

Why it matters

When a live conductor touches a metal case, the fault current must return to the source fast enough to trip a breaker or an RCD. The path it takes is defined by the earthing system — and each system needs different protection.

The three residential systems

  • TN-S. A separate protective conductor (PE) comes in with the supply. Fault currents are large, breakers trip fast. The panel just connects PE to the PE busbar.
  • TN-C-S. The supply arrives with a combined PEN conductor which is split into N and PE before your dwelling panel — at the building service entrance. Splitting PEN inside an apartment panel is prohibited: a broken PEN upstream would put mains voltage on every earthed case.
  • TT. There is no usable PE from the supply; a local earth electrode provides the earth. The fault current is limited by the electrode resistance (tens of ohms) and is far too small to trip a breaker — an RCD at the panel input is mandatory, and the electrode resistance must be confirmed by measurement.

No PE conductor? Do not guess

If no separate green-yellow PE enters your home, the system cannot be deduced from the wall: guessing TN-C-S means an illegal PEN split, guessing TT assumes an electrode that may not exist. The earthing system must be designed and verified by a licensed electrician. PlanMyPanel marks such projects explicitly and assumes the worst case (TT) until then.

PlanMyPanel is a planning aid, not a substitute for a professional. Final assembly and connection must be reviewed and approved by a licensed electrician.

Built on the EU HD 60364 series and the CIS wiring regulations (PUE).

© 2026 PlanMyPanel